12 Electrical connection
12.4.5

Extension unit EXU-SA

This extension unit has inputs for door mounted sensors, which can give presence impulse on
approach side and/or presence detection on swing path side. Relay output for error indication
or door indication is also integrated.
Functions
Blanking LED
2)
Door mounted sensors
DMPS:
Relay 1: Presence impulse (NC)
Relay 2: Presence detection (NC)
1)
If not used strap to "Ground".
2)
Remove strapping from terminals 2 and/or 3.
56
Monitoring of presence detection/DMPS.SS
Monitoring of presence impulse/DMPS.NS
No monitoring (both jumpers on)
Monitoring of presence detection and presence impulse
Blanking potentiometer
(Adjust the potentiometer to avoid presence detection sensor to
detect the wall. Range 55 - 90 degrees.)
Closed door indication / open door indication
Issue 2012-06-27
External error indication / KILL OUT / Lock
Open door indication / closed door
indication
NO
Relay output ("External error, KILL OUT, Lock
COM
indication" or "Open/closed door indication", see
above) 24 V, 1 A
NC
(+) 24 VDC
24 V DC
QTST
DMPS monitoring and reference for KILL (NC)
Presence detection (NC)/DMPS.SS
PDET
PIMP
Presence impulse (NC)/DMPS.NS
Ground
GND
(-) 0 VDC Ground
Remove strapping when connecting to
terminals 2 and/or 3
1)
1)
1007718-US-3.0