Signal
BHGStatRec
BHGInLen
BHGOutLen
BHGTimeout
BHGCycl
BHGRecGDNo
BHGRecGBZNo
BHGRecObjNo
BHGSendGDNo
BHGSendGBZNo
BHGSendObjNo
BHGMPI
BHGStop
BHGNotSend
NCCyclTimeout
NCRunupTimeout
ListMDecGrp
NCKomm
PLC Basic Program Solution Line (P3 sl)
Function Manual, 08/2005 Edition, 6FC5397-0BP10-0BA0
Type Type
Value range
I
Pointer
Q0.0 to Q124.0,
F0.0 to F252.0 or
DBn DBX0.0 to
DBXm.0
I
Byte
HHU default:
B#16#6 (6 bytes)
I
Byte
HHU default:
B#16#14 (20 bytes)
I
S5time
Recommendation:
700 ms
I
S5time
Recommendation:
100 ms
I
Int
HHU default: 2
I
Int
HHU default: 2
I
Int
HHU default: 1
I
Int
HHU default: 2
I
Int
HHU default: 1
I
Int
HHU default: 1
I
Bool
I
Bool
I
Bool
I
S5time
Recommendation:
200 ms
I
S5time
Recommendation:
50 s
I
Int
0...16
I
Bool
Detailed Description
2.12 Block descriptions
Remarks
Start address for status double
word for receiving data
from HHU: DW#16#00000400:
Timeout,
otherwise 0
Quantity of data received from
handheld unit
Quantity of data transmitted to
handheld unit
Cyclic sign-of-life monitoring for
handheld unit
Time reference for cyclic updating
of signals to handheld unit
Receive GD circle no.
or bus address
Receive GI no.
Object number for receive GI
Transmit GD circle no.
Transmit GI no.
Object number for transmit GI
1: Handheld unit coupled to MPI
(without SDB 210 config.)
Parameter HHU must be set to 2.
0: Start transmission
of handheld unit signals
1: Stop transmission
of handheld unit signals
0: Send and receive operation
activated
1: Receive handheld unit signals
only
Cyclic sign-of-life monitoring NCK
Power-up monitoring NCK
Activation of expanded
M group decoding
0: Not active
1...16: Number of M groups
PLC NC communications services
(FB 2/3/4/5/7:
Put/Get/PI_SERV/GETGUD)
true: active