External Power Supply For The Control Unit (Xpow); Di6 As A Ptc Sensor Input - ABB ACS880-104 Hardware Manual

Industrial drives, inverter modules
Hide thumbs Also See for ACS880-104:
Table of Contents

Advertisement

Notes:
1)
See section
The XD2D connector (page
2)
See chapter
The Safe torque off function (page
3)
0 = Acceleration/deceleration ramps defined by parameters 23.12/23.13 in use. 1 =
Acceleration/deceleration ramps defined by parameters 23.14/23.15 in use.
4)
Constant speed 1 is defined by parameter 22.26.
5)
See section
DIIL input (page
6)
Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by
DIO1 and DIO2.
7)
Determines whether DICOM is separated from DIOGND (ie. common reference for digital
inputs floats; in practice, selects whether the digital inputs are used in current sinking or
sourcing mode). See also
DICOM=DIOGND ON: DICOM connected to DIOGND. OFF: DICOM and DIOGND separate.
8)
Current [0(4)...20 mA, R
selected by switch AI1. Change of setting requires reboot of control unit.
9)
Current [0(4)...20 mA, R
selected by switch AI2. Change of setting requires reboot of control unit.

External power supply for the control unit (XPOW)

The control unit is powered from a 24 V DC, 2 A supply through terminal block XPOW. With
a type BCU control unit, a second supply can be connected to the same terminal block for
redundancy.

DI6 as a PTC sensor input

A PTC sensor can be connected to this input for motor temperature measurement as follows.
The sensor can alternatively be connected to FEN-xx encoder interface module. At the
sensor end of the cable, leave the shields unconnected or ground them indirectly via a
high-frequency capacitor with a few nanofarads, for example 3.3 nF / 630 V. The shield can
also be grounded directly at both ends if they are in the same ground line with no significant
voltage drop between the end points. See the firmware manual of the inverter unit for
parameter settings.
PTC
T
3.3 nF
> 630 V AC
WARNING!
As the inputs pictured above are not insulated according to IEC 60664, the
connection of the motor temperature sensor requires double or reinforced insulation
between motor live parts and the sensor. If the assembly does not fulfill the
requirement, the I/O board terminals must be protected against contact and must
not be connected to other equipment or the temperature sensor must be isolated
from the I/O terminals.
306).
306).
BCU-x2 ground isolation diagram (page
= 100 ohm] or voltage [0(2)...10 V, R
in
= 100 ohm] or voltage [0(2)...10 V, R
in
+24VD
DI6
Control units of the drive 305
313).
311).
> 200 kohm] input
in
> 200 kohm] input
in

Advertisement

Table of Contents
loading

Table of Contents