Definitions - ABB ACS880-104 Hardware Manual

Industrial drives, inverter modules
Hide thumbs Also See for ACS880-104:
Table of Contents

Advertisement

278 Technical data
Input
Inverter
ratings
unit
Frame
type
size
ACS880-
I
104- ...
A
1030A-7
2×R8i
1159
1170A-7
2×R8i
1316
1540A-7
3×R8i
1733
1740A-7
3×R8i
1958
2300A-7
4×R8i
2588
2860A-7
5×R8i
3218
3420A-7
6×R8i
3848

Definitions

U
Nominal AC supply voltage of drive system
N
I
Nominal rms input current
1
I
Nominal output current (available continuously with no over-loading)
2
P
Typical motor power in no-overload use
N
The horsepower ratings are typical NEMA motor sizes at 460 V (ACS880-104-xxxxA-5) and 575 V
(ACS880-104-xxxxA-7) respectively.
Apparent power in no-overload use
S
N
I
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
Ld
P
Typical motor power in light-overload use
Ld
I
Maximum output current. Available for 10 seconds at start; otherwise as long as allowed by drive
max
temperature.
I
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
Hd
P
Typical motor power in heavy-duty use
Hd
Note:
The ratings apply at an ambient temperature of 40 °C (104 °F).
The ratings apply to units without option +C132 (marine type approval). For ratings of
units with option +C132, see ACS880 +C132 marine type-approved drive modules and
module packages supplement (3AXD50000037752 [English])
To achieve the rated motor power given in the table, the rated current of the drive must
be higher than or equal to the rated motor current.
The DriveSize dimensioning tool available from ABB is recommended for selecting the
drive, motor and gear combination.
No-overload use
I
I
1
max
2
A
A
1550
1030
1760
1170
2310
1540
2610
1740
3450
2300
4290
2860
5130
3420
Output ratings
Light-overload
P
S
I
N
N
Ld
kW
kVA
A
1000
1231
989
1100
1398
1123
1400
1840
1478
1600
2080
1670
2000
2749
2208
2800
3418
2746
3200
4087
3283
Heavy-duty use
use
P
I
Ld
Hd
kW
A
900
770
1000
875
1400
1152
1600
1302
2000
1720
2400
2139
3200
2558
P
Hd
kW
710
800
1100
1200
1600
2000
2400

Advertisement