ABB ACS880-104 Hardware Manual page 310

Industrial drives, inverter modules
Hide thumbs Also See for ACS880-104:
Table of Contents

Advertisement

310 Control units of the drive
Analog inputs AI1 and AI2
(XAI:4 ... XAI:7).
Current/voltage input mode selection by
jumpers (ZCU-1x) or switches (BCU-x2)
Analog outputs AO1 and AO2 (XAO)
XD2D connector
RS-485 connection (X485) (BCU-x2 only)
Safe torque off connection (XSTO)
Safe torque off output (XSTO OUT) (BCU-
x2 only)
Control panel connection (X13)
Ethernet connection (XETH) (BCU-x2
only)
SDHC memory card slot (SD CARD)
(BCU-x2 only)
The terminals of the control unit fulfill the Protective Extra Low Voltage (PELV) requirements. The PELV re-
quirements of a relay output are not fulfilled if a voltage higher than 48 V is connected to the relay output.
Connector pitch 5 mm, wire size 2.5 mm
Current input: –20...20 mA, R
Voltage input: –10...10 V, R
Differential inputs, common mode range ±30 V
Sampling interval per channel: 0.25 ms
Hardware filtering: 0.25 ms, adjustable digital filtering up to 8 ms
Resolution: 11 bit + sign bit
Inaccuracy: 1% of full scale range
Connector pitch 5 mm, wire size 2.5 mm
0...20 mA, R
< 500 ohm
load
Frequency range: 0...300 Hz (ZCU-1x), 0...500 Hz (BCU-x2)
Resolution: 11 bit + sign bit
Inaccuracy: 2% of full scale range
Connector pitch 5 mm, wire size 2.5 mm
Physical layer: RS-485
Termination by jumper (ZCU-1x) or switch (BCU-x2)
Connector pitch 5 mm, wire size 2.5 mm
Physical layer: RS-485
Connector pitch 5 mm, wire size 2.5 mm
Input voltage range: -3...30 V DC
Logic levels: "0" < 5 V, "1" > 17 V.
Note: For the unit to start, both connections must be "1". This applies
to all control units (including drive, inverter, supply, brake, DC/DC
converter etc. control units), but true Safe torque off functionality is
only achieved through the XSTO connector of the drive/inverter
control unit.
Current consumption: 66 mA (continuous) per STO channel per R8i
module
EMC (immunity) according to IEC 61326-3-1
See also chapter
The Safe torque off function (page
Connector pitch 5 mm, wire size 2.5 mm
To STO connector of inverter module.
Connector: RJ-45
Cable length < 3 m
Connector: RJ-45
This connection is not supported by the firmware.
Memory card type: SDHC
Maximum memory size: 4 GB
2
= 100 ohm
in
> 200 kohm
in
2
2
2
2
2
313).

Advertisement

Table of Contents
loading

Table of Contents