78 Electrical installation
6. Strip the cable ends and conductors. When connecting to the drive I/O, also remove
the shield along with the outer sheathing, and use electrical tape or shrink tubing to
6. Strip the cable ends and conductors. When connecting to the drive I/O, also remove
contain the strands. Elsewhere, twist the outer shield strands into a bundle, crimp a
lug onto it and connect it to the nearest chassis grounding point.
7. Connect the conductors to appropriate terminals.
8. Refit any shrouds removed earlier.

Installing optional modules

7. Connect the conductors to appropriate terminals (see the circuit diagrams delivered
with the unit).
8. Fasten the shrouds (if any).
9. Close the doors.
Note:
Pay attention to the free space required by the cabling or terminals coming to the optional
modules.
1. Repeat the steps described in section
2. Ensure by measuring that the I/O terminals of the control unit (especially the relay output
3. Insert the module into a free option module slot on the control unit.
4. Fasten the module. For instructions, see the documentation of the optional module.
5. Connect the necessary wiring to the module following the instructions given in the
6. Tighten the grounding screw to a torque of 0.8 N·m.
the shield along with the outer sheathing, and use electrical tape or shrink tubing to
contain the strands. Elsewhere, twist the outer shield strands into a bundle, crimp a lug
onto it and connect it to the nearest chassis grounding point.
1
4

Installation of I/O extension and fieldbus adapter modules

WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or death,
or damage to the equipment can occur.
terminals) are safe.
documentation of the module.
1
2
3
2
4
3
5
5
Electrical safety precautions (page
Electrical installation 159
Keep as short as possible
SHIELD*
If no dedicated "shield" connector
is provided, ground the inner cable
shields to the chassis.
At the other end of the cable, leave
the shield unconnected, or connect
it to ground via a capacitor with a
value of a few nanofarads.
Where grounding clamps are not
available, twist the shield strands
into a bundle, crimp a lug terminal
onto it and fasten the lug to the
chassis. Secure the cable into
place with eg. cable ties.
144).