198 Maintenance

LEDs and other status indicators

Control panel and panel platform/holder LEDs

The ACX-AP-x control panel has a status LED. The control panel mounting platform or
holder has two status LEDs. For their indications, see the following table.
Location
LED
Control panel
Continuous green
Flickering green
Blinking green
Continuous red
Blinking red
Blinking blue (ACS-
AP-W only)
Flickering blue
(ACS-AP-W only)
Control panel
Red
mounting platform or
Green
holder (with the con-
trol panel removed)

R8i module LEDs

Frame R8i modules have three LEDs. For their indications, see the following table.
Location
LED
R8i module
FAULT
(continuous red)
ENABLE / STO
(continuous green)
ENABLE / STO
(continuous yellow)
POWER OK
(continuous green)

Reduced run

A "reduced run" function is available for inverter units consisting of parallel-connected inverter
modules. The function makes it possible to continue operation with limited current even if
one (or more) module is out of service, for example, because of maintenance work. In
principle, reduced run is possible with only one module, but the physical requirements of
operating the motor still apply; for example, the modules remaining in use must be able to
provide the motor with enough magnetizing current.
The wiring accessories needed during the procedure are available from ABB.
Indication
The unit is functioning normally.
Data is transferred between the PC and the unit through the USB
connection of the control panel.
There is an active warning in the unit.
There is an active fault in the unit.
There is a fault that requires the stopping and restarting of the
drive/converter/inverter.
The Bluetooth interface is enabled, in discoverable mode, and
ready for pairing.
Data is being transferred through the Bluetooth interface of the
control panel.
There is an active fault in the unit.
Power supply for the control unit is OK.
Indication
There is an active fault in the module.
The module is ready for use.
XSTO connectors are de-energized.
Supply voltage of the internal circuit boards is OK (> 21 V).