Definitions

f
Supply frequency
I
Continuous current consumption
cont
I
Calculated load current at start
start
P
Continuous input power
cont
U
Voltage requirement
N

Fuse data

Ferrules used with 400 V and 500 V units

Rating
Class
A rms
10
aR
15
aR
20
aR
25
aR
32
aR
50
aR
63
aR
80
aR
100
aR
125
aR
160
aR
200
aR

Ferrules used with 690 V units

Rating
Class
A rms
40
aR
100
aR
Example
Bussmann FWP-10A14F
Bussmann FWP-15A14F
Bussmann FWP-20A14F
Bussmann FWP-25A14F
Bussmann FWP-32A14F
Mersen 6,921 CP URQ 27x60/50
Mersen 6,921 CP URQ 27x60/63
Mersen 6,921 CP URQ 27x60/80
Mersen 6,921 CP URQ 27x60/100
Mersen 6,921 CP URQ 27x60/125
Mersen 6,921 CP URQ 27x60/160
Mersen 6,921 CP URQ 27x60/200
Example
Mersen 1021 CP URB 27x60/40
Mersen 1021 CP URB 27x60/100
Power
Clearing I
loss at I
n
2
W
A
s
4
22
5.5
75
6
180
7
320
7.6
600
16
610
21
860
24
1880
27
3210
30
6970
34
15000
38
30000
Power
Clearing I
loss at I
n
2
W
A
s
17
450
27
6000
Technical data 293
2
t
U
n
V
V
660
660
660 (IEC)
660
700 (UL)
660
660
690
690
690
690
690
690
690
690
2
t
U
n
V
V
1000
1000
1000