288 Technical data
Current
Switching frequency
Maximum recommended
motor cable length
Output terminals (Frame
R1i)
Output terminals (Frame
R2i)
Output terminals
(Frames R3i...R5i)
Output terminals
(Frames R6i and R7i)–
Side view
See section Ratings.
Frames R1i...R4i: 4.5 kHz (typical)
Frames R5i...R8i: 3 kHz (typical)
The switching frequency can vary per frame and voltage. For exact values, please
contact your local ABB representative.
*Frames R1i...R2i: 150 m (492 ft)
*Frames R3i...R7i: 300 m (984 ft)
Frame R8i and multiples: 500 m (1640 ft)
*Tested with 100 m (328 ft) for EMC Category C3. See standards and markings
information in Electrical planning instructions for ACS880 multidrive cabinets and
modules (3AUA0000102324 [English]).
Note: Longer cables cause a motor voltage decrease which limits the available
motor power. The decrease depends on the motor cable length and characteristics.
Contact ABB for more information. Note that a sine filter (optional) at the drive
output also causes a voltage decrease.
U2, V2, W2: 0.25 ... 4 mm
Ground: 1.5 N·m (13 lbf·in)
U2, V2, W2: 0.5 ... 6 mm
Ground: 1.5 N·m (13 lbf·in)
U2, V2, W2: 6 ... 70 mm
torque 4 N·m (30 lbf·in). Other conductor sizes can be used by replacing the original
lug with a suitable crimp ring terminal.
Ground: M5, torque 3 N·m (25 lbf·in)
Connector cover screws: Torque 3 N·m (25 lbf·in)
Screw size: M12 or ½". Tightening torque: 70 N·m (52 lbf·ft)
2
, 0.5 ... 0.6 N·m (4.4 ... 5.3 lbf·in)
2
, 1.2 ... 1.5 N·m (10.6 ... 13.3 lbf·in)
2
. Allen screw torque 15 N·m (11 lbf·ft), connection post