Errata
Power Supply Wiring Procedure Update
NOTE: The following applies to System 1010X, 1010BX, 1010DVX, 1010PVX, 1010GX,
1010GCX, 1010GCSX and 1010SPVX Flowmeter installation manuals.
Replace the "Power Connections" description and set up procedure with the following. Note that
paragraph numbers are different for all the above mentioned manuals. The example below is for
the 1010X manual.
NOTE: For flowmeters refer to drawings 1010X-7 (1 of 3) & 1010DX-7 (1 of 3) and
for Interface Detectors refer to drawings 1010BX-7 (1 of 3) & 1010BDX-7
(1 of 3).
2.2
POWER CONNECTIONS
2.2.1 INPUT POWER CONNECTOR (P8) AND FUSE (F1) LOCATIONS
The standard 1010X flow computer either requires 100/120/200 VAC or one of three 9-36 VDC
power sources for its power input. The power input is protected by a GMA 2A fuse (F1). Please
replace this fuse with the exact type if it becomes necessary to do so.
WARNING
Do not connect AC or
DC power to flowmeter
until the correct type of
input power is de-
termined. See P/N
tables on next page.
Contact with exposed
wiring may lead to fire,
electric shock, or seri-
ous personal injury.
WARNING
Connect power per instructions below.
See field manual for complete power
supply wiring procedures.
1010X-6SS2
Terminal
90-230 VAC
Number
(Single Phase)
1
Hot
Neutral
2
3
Ground
Sample Power Label Located Inside Rear
Housing Cover.
Siemens Hardware
ERRATA
This must be
1
connected to
Earth Ground.
2
3
E-1
Fuse (F1) GMA 2A
Cable
Clamp
AC
HOT NEU GND
DC
+
-
GND
1010FMA-45