Technical Data; 1.2. Input Voltage Ranges; 1.3. Phase Imbalance; 1.4. Output Power And Current Ratings - Invertek Drives Eco Optidrive ODV-3-220043-1F12-SN User Manual

Ac variable speed drive 0.75-250kw/1-350hp, 200-600v single and 3 phase input
Hide thumbs Also See for Eco Optidrive ODV-3-220043-1F12-SN:
Table of Contents

Advertisement

11. Technical Data

11.1. Environmental
Ambient Temperature Range
Maximum Altitude
Relative Humidity
Refer to section 1 1.7. Derating Information on page 71 for derating information.

11.2. Input Voltage Ranges

Depending upon model and power rating, the drives are designed for direct connection to the following supplies:
Model Number
ODV-3-x2xxxx-1xxx-xx
ODV-3-x2xxxx-3xxx-xx
ODV-3-x4xxxx-3xxx-xx
ODV-3-x5xxxx-3xxx-xx
ODV-3-x6xxxx-3xxx-xx

11.3. Phase Imbalance

All three phase Optidrive Eco units have phase imbalance monitoring. The maximum permissible voltage imbalance between any two
phases is 3% for full load operation.

11.4. Output Power and Current ratings

The following tables provide the output current rating information for the various Optidrive Eco models. Invertek Drives always
recommend that selection of the correct Optidrive is based upon the motor full load current at the incoming supply voltage.
Please note that the maximum cable length stated in the following tables indicate the maximum permissible cable length for the drive
hardware and does not take into consideration EMC compliance.
11.4.1. 200 – 240 Volt, 1 Phase Input Models
Output
Current
Frame
Capacity
Size
2
2
2
11
66 | Optidrive Eco User Guide | Version 3.05
Storage
Operational
Operational
Operational
Supply Voltage
200 – 240 Volts + / - 10%
200 – 240 Volts + / - 10%
380 – 480 Volts + / -10%
480 – 525 Volts + / - 10%
500 – 600 Volts + / - 10%
Typical Power Rating
A
kW
HP
4.3
0.75
1
7
1.5
2
10.5
2.2
3
All
-40 °C ... 60 °C
IP20
-10 ... 50°C without derating
IP55
-10 ... 40°C without derating
IP66
All
1000m without derating
All
=< 95% (no condensation permitted)
Phases
Nominal
Fuse or
Input
MCB
Current
(Type B)
A
8.5
10
15.2
25
19.3
25
Frequency
1
50 – 60 Hz
3
50 – 60 Hz
3
50 – 60 Hz
3
50 – 60 Hz
3
50 – 60 Hz
Maximum
Maximum Motor
Cable Size
Cable Length
sq.mm
AWG
m
8
4.3
100
8
7
100
8
10.5
100
www.invertekdrives.com
ft
330
330
330

Hide quick links:

Advertisement

Table of Contents
loading