3.12. IP66 (Nema 4X) Gland Plate and Lock Off
The use of a suitable gland system is required to maintain the appropriate IP / Nema rating. Cable entry holes will need to be drilled
to suit this system. Some guidelines sizes are defined below:
Please take care when drilling to avoid leaving any particles within the product.
Cable Gland recommended Hole Sizes & types:
Drive size
Min Gland Rating
Size 2
Size 3
U L rated ingress protection ("Type ") is only met when cables are installed using a UL recognized bushing or fitting for a
flexible-conduit system which meets the required level of protection ("Type").
F or conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC.
N ot intended for rigid conduit system.
Power Isolator Lock Off
On the switched models the main power isolator switch can be locked in the 'Off' position using a 20mm standard shackle padlock
(not supplied).
IP66 / Nema 4X Unit Lock Off
www.invertekdrives.com
Hole Size
IP66
1 x 20.5mm and 2 x 28.3mm
IP66
1 x 20.5mm and 2 x 28.3mm
Imperial
1 PG13.5 and 2 PG21
1 x M20 and 2 x M25
1 PG13.5 and 2 PG21
1 x M20 and 2 x M25
Version 3.05 | Optidrive Eco User Guide | 17
Metric
3