3.10. Removing the Terminal Cover
3.10.1. Frame Sizes 2 & 3
OFF
PWR
3.10.2. Frame Size 4
3
3.11. Routine Maintenance
The drive should be included within the scheduled maintenance program so that the installation maintains a suitable operating
environment, this should include:
Ambient temperature is at or below that set out in the section 1 1. 1 . Environmental, with any relevant derating applied.
Heat sink fans (where fitted) freely rotating and are dust free.
If the drive is mounted within an enclosure:
o Ensure this is free from dust and condensation.
o Ensure sufficient ventilation of fresh clean cooling air is provided.
o Ensure any panel ventilation fans and air filters are clean and provide the correct required air flow.
C hecks should also be made on all electrical connections, ensuring screw terminals are correctly torqued; and that power cables
have no signs of heat damage.
16 | Optidrive Eco User Guide | Version 3.05