Mitsubishi Electric MR-J5 Series User Manual page 171

Ac servo system
Hide thumbs Also See for MR-J5 Series:
Table of Contents

Advertisement

For main circuit power supply [WG]
■For MR-J5W2
Total output
Total
of rotary
continuous
servo motors
thrust of
linear servo
motors
300 W or less
From over 300 W
150 N or less
to 600 W
Over 600 W
From over 150 N
1 kW or less
to 300 N
Over 1 kW
From over 300 N
2 kW or less
to 720 N
*1 When using the servo amplifier as an IEC/EN/UL/CSA standard compliant product, refer to "MR-J5 Safety Instructions and Precautions
for AC Servos".
*2 Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80
ms or less.
*3 The molded-case circuit breaker is the same regardless of whether a power factor improving AC reactor is used.
*4 Use a molded-case circuit breaker that has operation characteristics equal to or higher than Mitsubishi Electric general-purpose
products.
■For MR-J5W3
Total output
Total
of rotary
continuous
servo motors
thrust of
linear servo
motors
450 W or less
150 N or less
From over 450 W
From over 150 N
to 800 W
to 300 N
From over 800 W
From over 300 N
to 1.5 kW
to 450 N
*1 When using the servo amplifier as an IEC/EN/UL/CSA standard compliant product, refer to "MR-J5 Instructions and Cautions for Safe
Use of AC Servos".
*2 Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80
ms or less.
*3 The molded-case circuit breaker is the same regardless of whether a power factor improving AC reactor is used.
*4 Use a molded-case circuit breaker that has operation characteristics equal to or higher than Mitsubishi Electric general-purpose
products.
The motor circuit breaker (Type E combination motor controller) can also be used instead of a molded-case circuit breaker.
Servo amplifier
Rated input voltage
AC [V]
MR-J5W2-22G
200 to 240
MR-J5W2-44G
MR-J5W2-77G
MR-J5W2-1010G
MR-J5W3-222G
MR-J5W3-444G
Total output
Molded-case circuit breaker
*3*4
of direct drive
motors
Frame,
rated current
30 A frame 5 A
100 W or less
30 A frame 10 A
From over 100 W
30 A frame 15 A
to 252 W
From over 252 W
30 A frame 20 A
to 838 W
Total output
Molded-case circuit breaker
*3*4
of direct drive
motors
Frame,
rated current
30 A frame 10 A
252 W or less
30 A frame 15 A
From over 252 W
30 A frame 20 A
to 378 W
Input phase
Motor circuit breaker (Type E combination motor
controller)
Model
3-phase
MMP-T32
Fuse
*1
Voltage
Class
AC [V]
240
Semiconductor
Fuse
*1
Voltage
Class
AC [V]
240
Semiconductor
Rated voltage
AC [V]
240
6 OPTIONS AND PERIPHERAL EQUIPMENT
6.9 Molded-case circuit breakers, fuses, magnetic contactors
Magnetic
contactor
*2
Current
Voltage
[A]
AC [V]
15
700
S-T10
20
20
30
S-T21
Magnetic
contactor
*2
Current
Voltage
[A]
AC [V]
20
700
S-T10
20
30
S-T21
SCCR [kA]
Rated current
[A] (heater
design)
6.3
50
8
13
18
8
13
6
169