5. Send 20 mA to the test set-up.
6. Increase the potentiometer value until the loop current reaches 19.95 mA.
7. Read the voltage across the potentiometer, which should be > 9 VDC. This is the
available system voltage at the maximum output.
Table 17 lists some compliance voltage readings at positioner terminals at several currents.
Table 17: Expected Voltage Range at Positioner Terminals
Current
4 mA
8 mA
12 mA
16 mA
20 mA
98 | =BHGE
Compliance Voltage
Requirement at
Positioner Terminals
11 V
10.5 V
10 V
9.5 V
9 V
Expected Voltage Measured at
Positioner Terminals
© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
10 to 11 V
9.5 to 10.5 V
9 to 10 V
8.5 to 9.5 V
8 to 9 V