Configuration with Pushbuttons
To change the current configuration parameters:
1. On power up if the VI II ESD is not in NORMAL mode, switch to NORMAL mode. The
display alternates between POS and SIGNAL indicating NORMAL mode.
2. Press + to access MANUAL mode.
3. With MANUAL mode displayed, press * to select the MANUAL mode the display
alternates between POS –M and SIG indicating MANUAL mode.
4. Press * and SETUP appears.
5. Press * again;
6. Press the * button to access the CONFIGuration menu.
7. Set the configuration parameters: Air Action, Air Pressure Units and Language. For
each parameter:
a. Press * to access and change the parameter.
b. Press + to move to the next parameter.
c. Press + to return to SETUP.
d. Press + to return to NORMAL mode.
64 | =BHGE
CONFIG appears.