Table 6 lists each display menu and provides a functional description of the menu, including pa-
rameters, where applicable.
Pushbutton Menu
NORMAL
MANUAL
SETUP
CONFIG
CALIB
PST CONF
VIEW DATA
VIEW ERR
CLR ERR
RUN PST
56 | =BHGE
Table 6: Pushbutton Display Menus
Runs the SVI II ESD in normal operating mode, displays position,
signal and pressure.
Executes manual mode in which the valve does not respond to
input signal and you can adjust position manually. In MANUAL the
valve responds to the Trip signal in addition to responding to
®
HART
. MANUAL menu provides access to SETUP.
Provides access to lower level setup menus; configuration (CON-
FIG), calibration (CALIB) and PST configuration.
Sets the following parameters: ATO/ATC, Pressure units, display
language.
Calibrates the SVI II ESD by running the STOPS (find stops) and
TUNE (autotune) functions.
Configures the following PST parameters: TRAVEL (range in a per-
centage of 100% travel over for partial stroke testing to occur),
PMIN (minimum amount of pressure allowed during PST), MAX
TIME (maximum amount of time in seconds allowed for partial
stroke), RAMPSPEED.
Displays the parameters set in CONFIG and PST CONF.
Displays all current errors.
Clears current errors, one at a time.
Executes PST (Partial Stroke Testing).
Function/Parameters