Checking Switch Operation

ValVue Commands

This procedure gives an example, using the settings in Figure 26, to see if a switch is operating:
1. Click the Configure tab, click and Figure 26 appears.
2. Switch from Normally Opened to Normally Closed or vice versa, click OK and Apply
Changes.
3. Click the Check tab.
4. Select Command 142 Read Switches from the pulldown list and click Send Cmd.
The information field below populates with the configured switch states.
Ensure that the switch just reconfigured has changed state.
96 | =BHGE
Figure 26 I/O Configure
© 2018 Baker Hughes, a GE company, LLC. All rights reserved.