Single Acting PST Controller
WARNING
The supply and output connections for the SVI II ESD, located on bottom of the pneumatic block,
are 1⁄4" NPT threaded. Output is toward the front, supply is toward the back.
Maximum allowable air supply pressure to the SVI II ESD varies according to actuator, valve size,
and valve type. Refer to the serial plate of the valve to know the specified supply pressure; it must
never be less than the maximum spring pressure +10 psi.
1. Install the tubing to the air supply port (S
2. For a single acting actuator - pipe the outbound air from the output pressure port
I) to the actuator.
(
3. Air supply:
38 | =BHGE
Isolate the valve from the process and disconnect air tubing from
the PST Controller. Disconnect air fully to avoid injury or process
damage.
Supply pressure for single acting SVI II ESD: 
30 -120 psi (2.07 - 8.28 bar) (207- 827.6 kPa)
Minimum tubing diameter 1⁄4" (6 mmx4 mm)
Supply
Figure 11 Air Ports on Single Acting PST Controller
).
Output
© 2018 Baker Hughes, a GE company, LLC. All rights reserved.