Mounting The Svi Ii Esd On Reciprocating Valves - Baker Hughes Masoneilan SVI II ESD Quick Start Manual

Sil3 emergency shutdown device & pst controller
Table of Contents

Advertisement

Mounting the SVI II ESD on Reciprocating Valves

The process of mounting the SVI II ESD on a reciprocating valve consists of mounting the unit on
the actuator that is attached to the valve. This section describes the procedure for mounting the
SVI II ESD on Reciprocating Valves (using Masoneilan's 87⁄88 Multi-Spring actuators as an exam-
ple).
Mounting the SVI II ESD on a Reciprocating Actuator
Tools required:
1. Ensure that the lever is pinned to the magnet assembly and held securely by an
M5 flat head screw to ensure that the magnet axis is vertical when the lever is in
the valve closed position. Tighten the lever screw securely. Refer to Figure 6.
2. Mount the SVI II ESD reciprocating mounting bracket to the actuator using two (2)
5⁄16 - 18 UNC cap screws.The mounting location of the bracket depends on the
size and stroke of the actuator. Refer to Figure 7 and Table 3 on page 32.
30 | =BHGE
7⁄16" Combination Wrench (2 required)
3⁄8" Combination Wrench
1⁄2" Combination Wrench
Phillips Head Screw Driver
5 mm Hex Key Wrench
Figure 6 Magnet Holder for Reciprocating Valves
Figure 7 Reciprocating Valve Mounting Bracket
Pin
M5 Flat head screw
© 2018 Baker Hughes, a GE company, LLC. All rights reserved.