7. The Raw Position Sensor value measured must in accordance with Table 2 on
page 27.
ValVue ESD Connected Devices Screen

Checking Actuator, Linkages, or Rotary Adapter

Verify that the mounting has not been damaged in shipment for a pre-mounted SVI II ESD, phys-
ically inspect the actuator, linkage. Record the following information for the configuration check-
out:
NOTE
Verify Mounting and Linkage Adjustment
Inspect the mounting and make any needed adjustments before running the PST Controller and
checking the digital configuration.
34 | =BHGE
Figure 10 ValVue ESD for Checking Magnet Position
Valve Air to Open (ATO) or Air to Close (ATC)
Actuator pressure rating
Actuator bench range
Inherent trim characteristic of the control valve; linear, equal percentage, or
other.
For the aforementioned information, refer to the valve data sheet
or model number of control valve.
ValVue ESD Check Screen