Where the protection type depends on wiring glands, the glands must be certified for the type of
protection required.
The metal housing is a die-casting alloy, which is predominately aluminum.
Before powering the SVI II ESD:
1. Verify that the pneumatic and electronic cover screws are tightened. This is important to
maintain the ingress protection level and the integrity of the flameproof enclosure.
2. If the Installation is Intrinsically Safe, then check that the proper barriers are installed and the
field wiring meets local and national codes for an I.S. installation. Never install a device, which
was previously installed without an intrinsically safe barrier, in an intrinsically safe system.
3. Under normal operation, compressed supply gas is vented from the SVI II ESD to the
surrounding area, and may require additional precautions or specialized installations.
4. If the Installation is Non-Incendive, then check that all the electrical connections are made to
Approved Devices and wiring meets local and national codes.
5. Verify that the markings on the label are consistent with the application.
6. Verify that the air supply pressure can not exceed:
a. For Single Acting 100 PSI (6.8 Bar)
4

MODEL NUMBER DESCRIPTION OF SVI II ESD

SVI2-
a
1
2
3
4
5
ESD - Emergency
6
Shutdown
Style
Regional Certifications Include: CU-TR, Nepsi, CCOE, Inmetro, Kosha,IA
5

FLAMEPROOF AND DUST IGNITION PROOF REQUIREMENTS

5.1 General
x The 1/2 inch NPT fittings must enter the housing at least five full turns.
x The cover flange must be clean and free of corrosion products.
Doc Number
ES-727
Revision
W
Filename
ES-727.DOC
Copyright 2017 as an unpublished trade secret. This document and all information herein is the property of Dresser LLC. It is confidential
and must not be made public or copied and is subject to return upon demand.
82 | =BHGE
b
c
Single
Standard
Acting
Flow
High
Capacity
Pneumatics
Capacity
PDR ECO-
11/15/2017
0029774
d
e
ASD w/ HART
Display
DSD w/ HART
Buttons
Industrial
Plug-in
Electronics
Module
(MNCB)
Display
Buttons
Offshore
Display
Electronics
Communication
Page 4 of 13
© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
f
g
Retransmit
Digital Out
A/DSD w/
HART
FM, CSA, ATEX,
Option
Written By
P.Levesque
Checked
T.Kabir
Approved
T. Kabir
h
FM, CSA ATEX
(XP, DIP, IS, NI)
IEC, Regional,
SIL3
Hazardous
Certification
13DEC2006
10JAN2007
10JAN2007

Advertisement

Table of Contents
loading

This manual is also suitable for:

Masoneilan svi ii esd sil3

Table of Contents