II 2G Ex db mb IIC T6..T4 Gb
II 2D Ex tb IIIC T96°C Db
FM17ATEX0093X
II 3G Ex ic IIC T6..T4 Gc
II 3D Ex tc IIIC T96°C Dc
(IEC)
IECEx FMG 07.0007X
Ex ia IIC T6..T4 Ga
Ex db mb IIC T6..T4 Gb
Ex tb IIIC T96°C Db
Ta=-40°C to +85°C
IP66
7.3
Operating Ranges
7.3.1 Temp: -40°C to +85°C
7.3.2 Voltage: 30 Volts
7.3.3 Pressure: 150 psig (1.03MPa)
7.3.4 Current: 4-20mA
7.4
Enclosure Type
Type 4X-IP66
7.5
Temperature Code
T6 Ta=60°C, T5 Ta=75°C, T4 Ta=85°C
7.6
Notes Related to Explosionproof Rating
DO NOT OPEN EVEN WHEN ISOLATED WHEN EXPLOSIVE ATMOSPHERES ARE
PRESENT
7.7
Notes Related to Intrinsic Safety
1) REFER TO ES-727 FOR ADDITIONAL CAUTIONS OR WARNINGS
2) Supply Connection Wiring Rated for 5ºC Above Max Ambient
3) PERMANENTLY MARK THE PROTECTION TYPE CHOSEN. ONCE THE TYPE
HAS BEEN MARKED, IT CAN NOT BE CHANGED
7.8
Model Code:
SVI2-abcdefgh
Doc Number
ES-727
Revision
W
Filename
ES-727.DOC
Copyright 2017 as an unpublished trade secret. This document and all information herein is the property of Dresser LLC. It is confidential
and must not be made public or copied and is subject to return upon demand.
86 | =BHGE
(see section 4 above for explanation)
PDR ECO-
11/15/2017
0029774
{Flameproof/Encapsulation, gas}
{Protection by Enclosure, dust}
{Certificate Number}
{Intrinsically Safe, gas}
{Protection by Enclosure, dust}
{Certificate Number}
{Intrinsically Safe}
{Explosionproof, gas}
{Protection by enclosure, dust}
{Operating Temperature}
{Ingress Protection}
Written By
Checked
Page 8 of 13
Approved
© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
P.Levesque
13DEC2006
T.Kabir
10JAN2007
T. Kabir
10JAN2007