Viewing Configuration Data
To view SVI II ESD configuration data:
1. Access the VIEW DATA menu from the MANUAL menu by pressing the + button.
2. Press * to examine the configuration.
3. Press + to scroll through and observe the factory configuration.
4. Press + until MANPOS appears.
5. Select with *.
When the adjustment screen appears.
6. Stroke the valve open by holding + down. The rate of set point change is slow to
begin, but increases speed while the + is pressed.
7. Stroke the valve to several values.
8. Verify the action is as desired.
Configuration
Parameter
Air Action
Air Pressure Units
Language
Viewing Status Messages
To view SVI II ESD status messages:
1. Press + and * to select VIEW ERR.
2. Observe any internal errors. For example, there should be a RESET status caused
by powering up. If the positioner was powered without air a Position Error or
POSERR can appear.
3. Press + to view all faults.
4. Press * to return to MANual menu.
5. Press + until CLR ERR appears.
6. Press * CLR ERR. WAIT is displayed for a second or two.
© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
Table 8: VIEWDATA Settings
Typical Setting
ATO
PSI
ENGLISH
Optional Setting
ATC
BAR
FRENCH, GERMAN, ITALIAN, PORTUGUESE,
SPANISH, JAPANESE (simplified)
Masoneilan SVI II ESD Quick Start Guide =| 65
KPA