Mounting The Svi Ii Esd With Namur Kits - Baker Hughes Masoneilan SVI II ESD Quick Start Manual

Sil3 emergency shutdown device & pst controller
Table of Contents

Advertisement

Dismantling the SVI II ESD from Rotary Valves
WARNING
To remove the SVI II ESD PST Controller from a rotary valve perform Steps 1 - 9 on page 25 in re-
verse.

Mounting the SVI II ESD with NAMUR Kits

There are two versions of this kit:
20 and 30 mm Mounting
Tools required:
Refer to Figure 4 for this procedure.
To mount using this kit:
1. Attach the mounting bracket to the valve actuator using four (4) M5 x 0.8 x 10
flat-head cap screws.
Quarter Turn 
Mounting Plate
2. Place the indicator disk with metal insert over the valve actuator shaft and secure
using an M6 x 1.0 x 45 socket-head screw.
28 | =BHGE
Before carrying out any work on the device, power off the
instrument or ensure that the device's location conditions for
potentially explosive atmosphere permit the safe opening of the
cover.
20 and 30 mm
50 mm
3 mm hex key
4 mm hex key
Figure 4 Namur 20/30 mm Mounting Kit
Mounting Bracket
Indicator Disc Bracket
© 2018 Baker Hughes, a GE company, LLC. All rights reserved.