Baker Hughes Masoneilan SVI II ESD Quick Start Manual page 85

Sil3 emergency shutdown device & pst controller
Table of Contents

Advertisement

7.1
Manufacturers Name and Location
Dresser LLC.
12970 Normandy Blvd.
Jacksonville FL 32221 USA
7.2
Summary of Agency Markings
(Factory Mutual)
In group a xp installations conduit seal required within 18 inches of enclosure
IS – CL I/II/III; DIV 1; GP A, B, C, D, E, F, G
XP – CL I; DIV 1; GP A, B, C, D
NI – CL I; DIV 2; GP A, B, C, D
DIP – CL II/III; DIV 1; GP E, F, G
S – CL II/III; DIV 2; GP F, G
CL I; DIV 1; GP B, C, D
CL II; DIV 1; GP E, F, G
CL III, DIV 1
IS – CL I; DIV 1; GP A, B, C, D
IS – CL II; DIV 1; GP E, F, G
IS – CL III; DIV 1
(ATEX)
FM17ATEX0072X
II 1G Ex ia IIC T6..T4 Ga
II 1D Ex ia IIIC T96°C Da
Doc Number
ES-727
Revision
W
Filename
ES-727.DOC
Copyright 2017 as an unpublished trade secret. This document and all information herein is the property of Dresser LLC. It is confidential
and must not be made public or copied and is subject to return upon demand.
© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
PDR ECO-
11/15/2017
0029774
{Certifying Agency}
{Intrinsically Safe}
{Explosionproof}
{Non-Incendive}
{Dust Ignitionproof}
{Special Protection}
{Certifying Agency}
{Explosionproof, gas}
{Explosionproof, dust}
{Explosionproof, fiber}
{Intrinsically Safe, gas}
{Intrinsically Safe, dust}
{Intrinsically Safe, fiber}
{Explosion Protected Mark}
{CE Conformity Marking, QAN Notified
Body Number}
{Certificate Number}
{Intrinsically Safe, gas}
{Intrinsically Safe, dust}
Written By
Checked
Page 7 of 13
Approved
Masoneilan SVI II ESD Quick Start Guide =| 85
P.Levesque
13DEC2006
T.Kabir
10JAN2007
T. Kabir
10JAN2007