AutoTune and Stops
This procedure takes 3 to 10 minutes and strokes the valve in large and small steps to set the
PID parameters for best positioning response.
To autoTUNE the SVI II ESD:
1. Press * to begin the autoTUNE procedure.
Numerical messages display, indicating the procedure is working.
2. TUNE appears when autoTUNE is complete.
3. Press + repeatedly until
4. Press * to return to SETUP menu
by the current calibrator.
5. Stroke the valve through its range to verify that the movement is as desired.
6. Press + to return to SETUP.
7. Press + to return to NORMAL mode.
Check-out with a HART
®
Connect the HART
to the product manual for the HART
Input Signal
Be sure that the configuration lock jumper is in the unlock position. When the jumper is in the lock
position (shorting the two-pin header) the handheld is not permitted to make any changes; how-
ever, parameters are readable. If fault messages appear, they must be handled before proceed-
®
ing with HART
communications. For example, the following message appears if the instrument
has been serviced and the air is not connected.
© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
Handheld Communicator
®
Handheld Communicator (HHC) to the SVI II ESD as shown in Figure 22. Refer
®
Figure 22 SVI II ESD HART
SETUP appears.
CALIB appears. The valve moves to the value set
Communication devices.
Configuration
Lock Jumper
®
Communicator Connections
20.00 mA
+
GE DPI620
Masoneilan SVI II ESD Quick Start Guide =| 67
-