Calibration - Baker Hughes Masoneilan SVI II ESD Quick Start Manual

Sil3 emergency shutdown device & pst controller
Table of Contents

Advertisement

Calibration

WARNING
To calibrate the SVI II ESD:
1. On power up if the SVI II ESD is not in NORMAL mode, switch to NORMAL mode.
The display alternates between POS and SIGNAL indicating NORMAL mode.
2. Press + to access MANUAL mode.
3. With MANUAL mode displayed, press * to select the MANUAL mode the display
alternates between POS –M and SIG indicating MANUAL mode.
4. Press * and SETUP appears.
5. Press * again;
6. Press + to display
7. Select CALIB by pressing *. STOPS appears.
8. Press * to activate the Find Stops calibration procedure.
The valve moves full open and back to full closed.
9.
Observe all warnings.
10. Press * to cause the valve to stroke and to automatically calibrate valve travel.
11. After the STOPS procedure finishes, press + twice until TUNE appears.
66 | =BHGE
In order to calibrate the SVI II ESD, it must be in SETUP mode.
CONFIG appears.
CALIB.
© 2018 Baker Hughes, a GE company, LLC. All rights reserved.