5.2.1
Configure Mass Flow Measurement Unit
Display
OFF-LINE MAINT→OFF-LINE CONFG→UNITS→MASS
ProLink II
ProLink→Configuration→Flow→Mass Flow Units
Field Communicator
Configure→Manual Setup→Measurements→Flow→Mass Flow Unit
Mass Flow Measurement Unit specifies the unit will be used for the mass flow rate. The unit used for mass
total and mass inventory is derived from this unit.
Procedure
Set Mass Flow Measurement Unit to the desired unit.
The default setting for Mass Flow Measurement Unit is g/s (grams per second).
Tip
If the measurement unit you want to use is not available, you can define a special measurement unit.
Options for Mass Flow Measurement Unit
The transmitter provides a standard set of measurement units for Mass Flow Measurement Unit, plus one
user-defined special measurement unit. Different communications tool use different labels for the units.
Options for Mass Flow Measurement Unit are shown in Table 5-1 .
Table 5-1
Options for Mass Flow Measurement Unit
Unit description
Grams per second
Grams per minute
Grams per hour
Kilograms per second
Kilograms per minute
Kilograms per hour
Kilograms per day
Metric tons per minute
Metric tons per hour
Metric tons per day
Pounds per second
Pounds per minute
Pounds per hour
Pounds per day
Short tons (2000 pounds)
per minute
Configuration and Use Manual
Display
G/S
G/MIN
G/H
KG/S
KG/MIN
KG/H
KG/D
T/MIN
T/H
T/D
LB/S
LB/MIN
LB/H
LB/D
ST/MIN
Label
ProLink II
g/s
g/min
g/hr
kg/s
kg/min
kg/hr
kg/day
mTon/min
mTon/hr
mTon/day
lbs/s
lbs/min
lbs/hr
lbs/day
sTon/min
Configure process measurement
Field Communicator
g/s
g/min
g/h
kg/s
kg/min
kg/h
kg/d
MetTon/min
MetTon/h
MetTon/d
lb/s
lb/min
lb/h
lb/d
STon/min
65