4.3.1
HART security
HART security may be enabled on the 9739 MVD transmitter. To configure the transmitter using HART
protocol, you must disable HART security.
4.3.2
Default values and ranges
Default values and ranges for the most commonly used parameters are provided in Appendix A.
4.4
Configure the primary mA output to report mass flow
rate in a user-selected measurement unit
Note
This procedure assumes that you are starting from the factory-default configuration.
Procedure
1.
Make a connection from the Field Communicator to your transmitter.
2.
Navigate to the On-Line Menu.
3.
Set the measurement unit for mass flow rate.
a.
Press Configure→Manual Setup→Measurements→Flow→Mass Flow Unit.
b.
Select the desired measurement unit from the list.
c.
Press the left arrow until you are returned to the Manual Setup menu.
4.
Configure the mA output.
a.
Press Inputs/Outputs→mA Output 1→Primary Variable.
b.
Select Mass Flow Rate from the list.
c.
Press ENTER until you are returned to the mA Output 1 menu.
d.
Press mA Output Settings.
e.
Press PV LRV and enter an appropriate value for Lower Range Value (LRV).
Lower Range Value specifies the value of Mass Flow Rate to be represented by an output level of
0 mA or 4 mA.
f.
Press ENTER.
g.
Press PV URV and enter an appropriate value for Upper Range Value (LRV).
Upper Range Value specifies the value of Mass Flow Rate to be represented by an output level
of 20 mA.
h.
Press ENTER.
5.
(Optional) Press Overview→Shortcuts→Variables→Outputs→Current (mA output 1) and observe the mA
output reading.
Configuration and Use Manual
Quick start with the Field Communicator
53