This function is accessed from the totalizer value on the display. If the appropriate totalizer is not
configured as a display variable, the operator will not be able to reset it.
6.2.3
Enable or disable the Acknowledge All Alarms display command
Display
OFF-LINE MAINT→OFF-LINE CONFG→DISPLAY→ALARM
ProLink II
ProLink→Configuration→Display→Display Options→Display Ack All Alarms
Not available
Field Communicator
You can control whether or not the operator will be able to use a single command to acknowledge
all alarms from the display.
Procedure
Enable or disable Acknowledge All Alarms as desired.
Option
Enabled (default)
Disabled
Note
To acknowledge alarms from the display, the operator must have access to the alarm menu, whether
Acknowledge All Alarms is enabled or disabled.
6.3

Configure security for the display menus

Display
OFF-LINE MAINT→OFF-LINE CONFG→DISPLAY→OFFLN
ProLink II
ProLink→Configuration→Display→Display Options→Display Offline Menu
Field Communicator
Not available
You can control operator access to different sections of the display off-line menu, and you can control
whether or not a password is required at specific entry points.
Procedure
1.
To control operator access to the maintenance section of the off-line menu, enable or disable
Off-Line Menu.
Configuration and Use Manual
Configure device options and preferences
Description
Operators can use a single display command to
acknowledge all alarms at once.
Operators cannot acknowledge all alarms at once.
They must acknowledge alarms individually.
105