Configure Events - Emerson Micro Motion 9739 MVD Configuration And Use Manual

Hide thumbs Also See for Micro Motion 9739 MVD:
Table of Contents

Advertisement

Integrate the meter with the control system
7.7

Configure events

Display
Not available
ProLink II
ProLink→Configuration→Events
Field Communicator
Configure→Alert Setup→Discrete Events
An event occurs if the real-time value of a user-specified process variable moves past a user-defined
setpoint. Events are used to provide notification of process changes or to perform specific transmitter
actions if a process change occurs.
The 9739 MVD transmitter supports two event models:
• Basic event model
• Enhanced event model
7.7.1
Configure a basic event
Display
Not available
ProLink II
ProLink→Configuration→Events
Field Communicator
Configure→Alert Setup→Discrete Events
A "basic" event is used to provide notification of process changes. A basic event occurs (is ON) if the
real-time value of a user-specified process variable moves above (HI) or below (LO) a user-defined
setpoint. You can define up to two basic events. Event status can be queried via digital communications,
and a discrete output can be configured to report event status.
Procedure
1.
Select Event 1 or Event 2 from Event Number.
2.
Specify Event Type.
HI
LO
3.
Assign a process variable to the event.
146
The event will occur if the value of the assigned process variable (x) is
greater than the setpoint (Setpoint A), endpoint not included.
x > A
The event will occur if the value of the assigned process variable (x) is less
than the setpoint (Setpoint A), endpoint not included.
x < A
Micro Motion 9739 MVD Transmitters