Rtds 7 To 10 - GE 489 Instruction Manual

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

4 SETPOINT PROGRAMMING
T
RTD #7
T
[ENTER] for more
RTDs 7 through 10 default to Bearing RTD type. There are individual alarm and trip configurations for each RTD. This
allows one of the RTDs to be turned off if it malfunctions. The alarm level and the trip level are normally set slightly above
the normal running temperature, but below the bearing temperature rating. Trip voting has been added for extra reliability in
the event of RTD malfunction. If enabled, a second RTD must also exceed the trip temperature of the RTD being checked
before a trip will be issued. If the RTD is chosen to vote with itself, the voting feature is disabled. Each RTD name may be
changed if desired.
GE Power Management
ð
RTD #7 APPLICATION:
ENTER
Bearing
ESCAPE
RTD #7 NAME:
ESCAPE
MESSAGE
RTD #7 ALARM:
ESCAPE
Off
MESSAGE
ASSIGN ALARM
ESCAPE
RELAYS (2-5): ---5
MESSAGE
RTD #7 ALARM
ESCAPE
TEMPERATURE: 80°C
MESSAGE
RTD #7 ALARM
ESCAPE
EVENTS: Off
MESSAGE
RTD #7 TRIP:
ESCAPE
Off
MESSAGE
RTD #7 TRIP VOTING:
ESCAPE
RTD #7
MESSAGE
ASSIGN TRIP
ESCAPE
RELAYS (1-4): 1---
MESSAGE
RTD #7 TRIP
ESCAPE
TEMPERATURE: 90°C
MESSAGE
489 Generator Management Relay
4.9 S8 RTD TEMPERATURE

4.9.3 RTDS 7 TO 10

Range: Stator, Bearing, Ambient, Other, None
Range: 8 alphanumeric characters
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to 5.
Range: 1 to 250°C in steps of 1
Range: On, Off
Range: Off, Latched, Unlatched
Range: RTD #1 to RTD #12
Range: Any combination of Relays 1 to 4
Range: 1 to 250°C in steps of 1
4
4-47