Advertisement

5 ACTUAL VALUES
Immediately prior to issuing a trip, the 489 takes a snapshot of generator parameters and stores them as pre-trip values;
this allows for troubleshooting after the trip occurs. The cause of last trip message is updated with the current trip and the
screen defaults to that message. All trip features are automatically logged as date and time stamped events as they occur.
This information can be cleared using the
trip is "No Trip To Date", the subsequent pretrip messages will not appear. Last Trip Data will not update if a digital input
programmed as Test Input is shorted.
T

ALARM STATUS

T
[ENTER] for more
GE Power Management
REAL POWER (MW)
ESCAPE
PRETRIP: 0.000
MESSAGE
REACTIVE POWER Mvar
ESCAPE
PRETRIP: 0.00 Hz
MESSAGE
APPARENT POWER MVA
ESCAPE
PRETRIP: 0.00 Hz
MESSAGE
HOTTEST STATOR RTD
ESCAPE
RTD #1: 0°C PreTrip
MESSAGE
HOTTEST BEARING RTD
ESCAPE
RTD #7: 0°C PreTrip
MESSAGE
HOTTEST OTHER RTD
ESCAPE
RTD #11: 0°C PreTrip
MESSAGE
AMBIENT RTD
ESCAPE
RTD#12: 0°C PreTrip
MESSAGE
ANALOG INPUT 1
ESCAPE
PreTrip: 0 Units
MESSAGE
ANALOG INPUT 2
ESCAPE
PreTrip: 0 Units
MESSAGE
ANALOG INPUT 3
ESCAPE
PreTrip: 0 Units
MESSAGE
ANALOG INPUT 4
ESCAPE
PreTrip: 0 Units
MESSAGE
Vab/Iab PreTrip:
ESCAPE
0.0 Ωsec.
MESSAGE
S1 489 SETUP \ CLEAR DATA \ CLEAR LAST TRIP DATA
ð
NO ALARMS
ENTER
ESCAPE
Input A ALARM
ESCAPE
STATUS: Active
MESSAGE
Input B ALARM
ESCAPE
STATUS: Active
MESSAGE
Input C ALARM
ESCAPE
STATUS: Active
MESSAGE
Input D ALARM
ESCAPE
STATUS: Active
MESSAGE
Input E ALARM
ESCAPE
STATUS: Active
MESSAGE
489 Generator Management Relay
Range: 0.000 to ±2000.000 MW
Not seen if VT CONNECTION is "None"
Range: 0.000 to ±2000.000 Mvar
Not seen if VT CONNECTION is "None"
Range: 0.000 to ±2000.000 MVA
Not seen if VT CONNECTION is "None"
Range: –50 to 250°C
Seen only if at least one RTD is "Stator"
Range: –50 to 250°C
Seen only if at least one RTD is "Bearing"
Range: –50 to 250°C
Seen only if at least one RTD is "Other"
Range: –50 to 250°C
Seen only if at least one RTD is Ambient
Range: –50000 to 50000
Not seen if VT Connection is "None"
Range: –50000 to 50000
Not seen if VT Connection is "None"
Range: –50000 to 50000
Not seen if VT Connection is "None"
Range: –50000 to 50000
Not seen if VT Connection is "None"
Range: 0 to 65535 Ωsec; 0 to 359°
Seen only if Loss of Excitation is enabled
setpoint. If the cause of last
5.2.3 ALARM STATUS
Range: N/A
Message seen when no alarms are active
Range: Active, Latched. The first line of this alarm
message
reflects
the
programmed. Status is Active if the condition
that caused the alarm is still present
Range: see Input A ALARM STATUS
Range: see Input A ALARM STATUS
Range: see Input A ALARM STATUS
Range: see Input A ALARM STATUS
5.2 A1 STATUS
5
Input
Name