Analog Inputs 1 To 4 - GE 489 Instruction Manual

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

4 SETPOINT PROGRAMMING
Table 4–8: ANALOG OUTPUT PARAMETER SELECTION
PARAMETER NAME
IA Output Current
IB Output Current
IC Output Current
Avg. Output Current
Neg. Seq. Current
Averaged Gen. Load
Hottest Stator RTD
–50 to +250°C or –58 to +482°F
Hottest Bearing RTD
–50 to +250°C or –58 to +482°F
Ambient RTD
–50 to +250°C or –58 to +482°F
RTDs 1 to 12
–50 to +250°C or –58 to +482°F
AB Voltage
BC Voltage
CA Voltage
Volts/Hertz
Frequency
Neutral Volt. (3rd)
Average Voltage
Power Factor
Reactive Power (Mvar)
Real Power
Apparent Power

Analog Inputs 1 to 4

Tachometer
Thermal Capacity Used
Current Demand
Mvar Demand
MW Demand
MVA Demand
T
ANALOG INPUT 1
T
[ENTER] for more
GE Power Management
RANGE / UNITS
0.00 to 20.00 × FLA
0.00 to 20.00 × FLA
0.00 to 20.00 × FLA
0.00 to 20.00 × FLA
0 to 2000% FLA
0.00 to 20.00 × FLA
0.00 to 1.50 × Rated
0.00 to 1.50 × Rated
0.00 to 1.50 × Rated
0.00 to 2.00 × Rated
0.00 to 90.00 Hz
0 to 25000 V
0.00 to 1.50 × Rated
0.01 to 1.00 lead/lag
–2.00 to 2.00 × Rated
–2.00 to 2.00 × Rated
0.00 to 2.00 × Rated
–50000 to +50000
0 to 7200 RPM
0 to 100%
0.00 to 20.00 × FLA
0.00 to 2.00 × Rated
0.00 to 2.00 × Rated
0.00 to 2.00 × Rated
ð
ANALOG INPUT1:
ENTER
Disabled
ESCAPE
ANALOG INPUT1 NAME:
ESCAPE
Analog I/P 1
MESSAGE
ANALOG INPUT1 UNITS:
ESCAPE
Units
MESSAGE
ANALOG INPUT1
ESCAPE
MINIMUM: 0
MESSAGE
ANALOG INPUT1
ESCAPE
MAXIMUM: 100
MESSAGE
BLOCK ANALOG INPUT1
ESCAPE
FROM ONLINE: 0 s
MESSAGE
489 Generator Management Relay
STEP
DEFAULT
MIN.
MAX
0.01
0.00
1.25
0.01
0.00
1.25
0.01
0.00
1.25
0.01
0.00
1.25
1
0
100
0.01
0.00
1.25
1
0
200
1
0
200
1
–50
60
1
–50
250
0.01
0.00
1.25
0.01
0.00
1.25
0.01
0.00
1.25
0.01
0.00
1.50
0.01
59.00
61.00
0.1
0.0
45.0
0.01
0.00
1.25
0.01
0.8 lag
0.8 lead
0.01
0.00
1.25
0.01
0.00
1.25
0.01
0.00
1.25
1
0
50000
1
3500
3700
1
0
100
0.01
0.00
1.25
0.01
0.00
1.25
0.01
0.00
1.25
0.01
0.00
1.25
4.12.2 ANALOG INPUTS 1 TO 4
Range: Disabled, 4-20 mA, 0-20 mA, 0-1 mA
Range: 12 alphanumeric characters
Range: 6 alphanumeric characters
Range: –50000 to 50000 in steps of 1
Range: –50000 to 50000 in steps of 1
Range: 0 to 5000 sec. in steps of 1
4.12 S11 ANALOG I/O