7.2 HARDWARE FUNCTIONAL TESTING
b) 0-1mA
1.
Alter the following setpoints:
S11 ANALOG I/O\ANALOG INPUT1\ANALOG INPUT1:
S11 ANALOG I/O\ANALOG INPUT1\ANALOG INPUT1 MINIMUM:
S11 ANALOG I/O\ANALOG INPUT1\ANALOG INPUT1 MAXIMUM:
Analog output values should be ±0.01 mA on the ammeter. Measured analog input values should be ±10 units. Force
2.
the analog outputs using the following setpoints:
S12 TESTING\TEST ANALOG OUTPUT\FORCE ANALOG OUTPUTS FUNCTION:
S12 TESTING\TEST ANALOG OUTPUT\ANALOG OUTPUT 1 FORCED VALUE:
Verify the ammeter readings as well as the measured analog input readings. View the measured values in:
A2 METERING DATA\ANALOG INPUTS
Table 7–4: ANALOG INPUT/OUTPUT TEST, 0 to 1 mA INPUT
ANALOG
EXPECTED
OUTPUT
AMMETER
FORCE
READING
VALUE
0%
0 mA
25%
0.25 mA
50%
0.50 mA
75%
0.75 mA
100%
1.00 mA
To verify the functionality of the output relays, perform the following steps:
1.
Using the setpoint:
S12 TESTING\TEST OUTPUT RELAYS\FORCE OPERATION OF RELAYS:
select and store values as per the table below, verifying operation
Table 7–5: OUTPUT RELAYS
FORCE
EXPECTED MEASUREMENT
OPERATION
( FOR SHORT)
SETPOINT
R1
7
NO NC

R1 Trip

R2 Auxiliary

R3 Auxiliary

R4 Auxiliary

R5 Alarm

R6 Service

All Relays

No Relays
R6 Service relay is failsafe or energized normally, operating R6 causes it to de-energize.
NOTE
7-8
0-1 mA
MEASURED AMMETER READING
(MA)
1
2
3
R2
R3
R4
R5
NO
NC
NO
NC
NO NC
NO NC


























489 Generator Management Relay
0
1000 (repeat for analog inputs 2 to 4)
Enabled
0% (enter %, repeat for outputs 2 to 4)
EXPECTED
ANALOG INPUT
READING
4
0 units
250 units
500 units
750 units
1000 units
R1 TRIP
ACTUAL MEASUREMENT
( FOR SHORT)
R6
R1
R2
NO
NC
NO
NC
NO
NC














7 TESTING
MEASURED ANALOG INPUT
READING (UNITS)
1
2
3

7.2.9 OUTPUT RELAYS

R3
R4
R5
R6
NO NC
NO NC
NO
NC
NO
GE Power Management
4