Current, Mw, Mvar, Mva Demand - GE 489 Instruction Manual

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

4 SETPOINT PROGRAMMING
T
CURRENT DEMAND
T
[ENTER] for more
T
MW DEMAND
T
[ENTER] for more
T
Mvar DEMAND
T
[ENTER] for more
T
MVA DEMAND
T
[ENTER] for more
GE Power Management
ð
CURRENT DEMAND
ENTER
PERIOD: 15 min.
ESCAPE
CURRENT DEMAND
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM
ESCAPE
RELAYS (2-5): ---5
MESSAGE
CURRENT DEMAND
ESCAPE
LIMIT: 1.25 x FLA
MESSAGE
CURRENT DEMAND
ESCAPE
ALARM EVENTS: Off
MESSAGE
ð
MW DEMAND
ENTER
PERIOD: 15 min.
ESCAPE
MW DEMAND
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM
ESCAPE
RELAYS (2-5): ---5
MESSAGE
MW DEMAND
ESCAPE
LIMIT: 1.25 x Rated
MESSAGE
MW DEMAND
ESCAPE
ALARM EVENTS: Off
MESSAGE
ð
Mvar DEMAND
ENTER
PERIOD: 15 min.
ESCAPE
Mvar DEMAND
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM
ESCAPE
RELAYS (2-5): ---5
MESSAGE
Mvar DEMAND
ESCAPE
LIMIT: 1.25 x Rated
MESSAGE
Mvar DEMAND
ESCAPE
ALARM EVENTS: Off
MESSAGE
ð
MVA DEMAND
ENTER
PERIOD: 15 min.
ESCAPE
MVA DEMAND
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM
ESCAPE
RELAYS (2-5): ---5
MESSAGE
MVA DEMAND
ESCAPE
LIMIT: 1.25 x Rated
MESSAGE
MVA DEMAND
ESCAPE
ALARM EVENTS: Off
MESSAGE
489 Generator Management Relay
4.11 S10 MONITORING

4.11.5 CURRENT, MW, MVAR, MVA DEMAND

Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to 5
Range: 0.10 to 20.00 × FLA in steps of 0.01
Range: On, Off
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to 5
Range: 0.10 to 20.00 × Rated in steps of 0.01
Range: On, Off
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to 5
Range: 0.10 to 20.00 × Rated in steps of 0.01
Range: On, Off
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to 5
Range: 0.10 to 20.00 × Rated in steps of 0.01
Range: On, Off
4
4-67