1 INTRODUCTION
ANALOG CURRENT OUTPUT
Type:
Active
Range:
4 to 20mA, 0 to 1 mA
(must be specified with order)
Accuracy:
±1% of full scale
4 to 20 mA max. load:
1.2 kΩ
0 to 1mA max. load:
10 kΩ
Isolation:
36 Vpk
(isolated with RTDs and analog inputs)
4 Assignable Outputs:
Phase A, B, C output current
3 phase average current
negative sequence current
generator load
hottest stator RTD
hottest bearing RTD
RTD # 1 to 12
AB voltage
BC voltage
CA voltage
average phase-phase voltage
volts/hertz
frequency
3rd harmonic neutral voltage
power factor
3 phase reactive power (Mvar)
3 phase real power (MW)
3 phase apparent power (MVA)
analog inputs 1 to 4
tachometer
thermal capacity used
I, Mvar, MW, MVA demands
Torque
OUTPUT RELAYS
Configuration:
6 electromechanical Form C relays
Contact Material:
silver alloy
Operate Time:
10 ms
Max Ratings for 100000 operations:
VOLTAGE
MAKE/CARRY
CTS
DC
30 V
10 A
RESISTIVE
125 V
10 A
250 V
10 A
DC
30 V
10 A
INDUCTIVE
125 V
10 A
L/R = 40 ms
250 V
10 A
AC
120 V
10 A
RESISTIVE
250 V
10 A
AC
120 V
10 A
INDUCTIVE
250 V
10 A
PF = 0.4
TERMINALS
Low Voltage (A, B, C, D terminals): 12 AWG max
High Voltage (E, F, G, H terminals): #8 ring lug,
10 AWG wire standard
GE Power Management
BREAK
MAX.
LOAD
0.2 s
30 A
10 A
300 W
30 A
0.5 A
62.5 W
30 A
0.3 A
75 W
30 A
5 A
150 W
30 A
0.25 A
31.3 W
30 A
0.15 A
37.5 W
30 A
10 A
2770 VA
30 A
10 A
2770 VA
30 A
4 A
480 VA
30 A
3 A
750 VA
489 Generator Management Relay
POWER METERING
Range:
0.000 to 2000.000 ±Mw, ±Mvar, MVA
Accuracy
at Iavg < 2 × CT:
±1% of
at Iavg > 2 × CT:
±1.5% of
WATTHOUR AND VARHOUR METERING
Description:
Continuous total of +watthours and
±varhours
Range:
0.000 to 4000000.000 MvarHours
Timing Accuracy:
±0.5%
Update Rate:
50 ms
DEMAND METERING
Metered Values:
Maximum Phase Current
3 Phase Real Power
3 Phase Apparent Power
3 Phase Reactive Power
Measurement Type:
Rolling Demand
Demand Interval:
5 to 90 minutes in steps of 1
Update Rate:
1 minute
Elements:
Alarm
GENERAL INPUT A TO G (DIGITAL INPUT)
Configurable:
Assignable Digital Inputs 1 to 7
Time Delay:
0.1 to 5000.0 s in steps of 0.1
Block From Online:
0 to 5000 s in steps of 1
Timing Accuracy:
±100 ms or ±0.5% of total time
Elements:
Trip, Alarm, and Control
SEQUENTIAL TRIP (DIGITAL INPUT)
Configurable:
Assignable to Digital Inputs 1 to 7
0.02 to 0.99 × rated MW in steps of 0.01
Pickup Level:
Low Forward Power / Reverse Power
Time Delay:
0.2 to 120.0 s in steps of 0.1
Pickup Accuracy:
see power metering
Timing Accuracy:
±100 ms or ±0.5% of total time
Elements:
Trip
FIELD BREAKER DISCREPANCY (DIGITAL INPUT)
Configurable:
Assignable to Digital Inputs 1 to 7
Time Delay:
0.1 to 500.0 s in steps of 0.1
Timing Accuracy:
±100 ms or ±0.5% of total time
Elements:
Trip
TACHOMETER (DIGITAL INPUT)
Configurable:
Assignable to Digital Inputs 4 to 7
RPM Measurement:
100 to 7200 RPM
>10%
Duty Cycle of Pulse:
101 to 175 × rated speed in steps of 1
Pickup Level:
Time Delay:
1 to 250 s in steps of 1
Timing Accuracy:
±0.5 s or ±0.5% of total time
Elements:
Trip and Alarm
OVERCURRENT ALARM
0.10 to 1.50 × FLA in steps of 0.01
Pick-up Level:
average phase current
Time Delay:
0.1 to 250.0 s in steps of 0.1
Pickup Accuracy:
as per Phase Current Inputs
Timing Accuracy:
±100 ms or ±0.5% of total time
Elements:
Alarm
1.2 SPECIFICATIONS
× 2 × CT × VT × VT full-scale
3
× 20 × CT × VT × VT full-scl.
3
1-5
1