5 ACTUAL VALUES
T

VOLTAGE METERING

T
[ENTER] for more
Measured voltage parameters will be displayed here. The V/Hz measurement is a per unit value based on Vab voltage/
measured frequency divided by VT nominal/nominal system frequency. Polar coordinates for measured phase and/or line
voltages are also shown using Va (wye connection) or Vab (open delta connection) as a zero angle reference vector. In the
absence of a voltage signal (Va or Vab), IA output current is used as the zero angle reference vector.
If
is programmed as "None" and
VT CONNECTION TYPE
ing flash message will appear when an attempt is made to enter this group of messages.
THIS FEATURE
NOT PROGRAMMED
GE Power Management
ð
Vab:
0
Vbc:
ENTER
Vca:
0
Volts
ESCAPE
AVERAGE LINE
ESCAPE
VOLTAGE: 0 Volts
MESSAGE
Van:
0
Vbn:
ESCAPE
Vcn:
0
Volts
MESSAGE
AVERAGE PHASE
ESCAPE
VOLTAGE: 0 Volts
MESSAGE
LINE A-B VOLTAGE:
ESCAPE
0 V
0° Lag
MESSAGE
LINE B-C VOLTAGE:
ESCAPE
0 V
0° Lag
MESSAGE
LINE C-A VOLTAGE:
ESCAPE
0 V
0° Lag
MESSAGE
PHASE A-N VOLTAGE:
ESCAPE
0 V
0° Lag
MESSAGE
PHASE B-N VOLTAGE:
ESCAPE
0 V
0° Lag
MESSAGE
PHASE C-N VOLTAGE:
ESCAPE
0 V
0° Lag
MESSAGE
PER UNIT MEASUREMENT
ESCAPE
OF V/Hz: 0.00
MESSAGE
FREQUENCY:
ESCAPE
0.00 Hz
MESSAGE
NEUTRAL VOLTAGE
ESCAPE
FUND: 0.0 V
MESSAGE
NEUTRAL VOLTAGE
ESCAPE
3rd HARM: 0.0 V
MESSAGE
TERMINAL VOLTAGE
ESCAPE
3rd HARM: 0.0 V
MESSAGE
IMPEDANCE Vab / Iab
ESCAPE
0.0 Ω sec.
MESSAGE
NEUTRAL VOLTAGE TRANSFORMER
489 Generator Management Relay
Range: 0 to 50000 V. Not seen if VT CONNECTION is
0
programmed as None.
Range: 0 to 50000 V. Not seen if VT CONNECTION is
programmed as None.
Range: 0 to 50000 V. Seen only if VT CONNECTION is
0
programmed as Wye.
Range: 0 to 50000 V. Seen only if VT CONNECTION is
programmed as Wye.
Range: 0 to 50000 V, 0 to 359°. Not seen if VT
CONNECTION is programmed as None.
Range: 0 to 50000 V, 0 to 359°. Not seen if VT
CONNECTION is programmed as None.
Range: 0 to 50000 V, 0 to 359°. Not seen if VT
CONNECTION is programmed as None.
Range: 0 to 50000 V, 0 to 359°. Seen only if VT
CONNECTION is programmed as Wye.
Range: 0 to 50000 V, 0 to 359°. Seen only if VT
CONNECTION is programmed as Wye.
Range: 0 to 50000 V, 0 to 359°. Seen only if VT
CONNECTION is programmed as Wye.
Range: 0.00 to 2.00. Not seen if VT CONNECTION is
programmed as None.
Range: 0.00 to 90.00 Hz. Not seen if VT CONNECTION
is programmed as None.
Range: 0.0 to 25000.0 V. Seen only if there is a neutral
voltage transformer.
Range: 0.0 to 25000.0 V. Seen only if there is a neutral
voltage transformer.
Range: 0.0 to 25000.0 V. Seen only if VT CONNECTION
is programmed as Wye.
Range: 0.0 to 6553.5 Ωsec., 0 to 359°
is "No" in S2 SYSTEM, the follow-
5.3 A2 METERING DATA
5.3.2 VOLTAGE METERING
5-13
5