GE 489 Instruction Manual page 170

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

6.3 MEMORY MAP
Table 6–1: 489 MEMORY MAP (Sheet 16 of 29)
ADDR NAME
FLEXCURVE TRIP TIME AT 12.0 × PU
1768
FLEXCURVE TRIP TIME AT 12.5 × PU
1769
FLEXCURVE TRIP TIME AT 13.0 × PU
176A
FLEXCURVE TRIP TIME AT 13.5 × PU
176B
FLEXCURVE TRIP TIME AT 14.0 × PU
176C
FLEXCURVE TRIP TIME AT 14.5 × PU
176D
FLEXCURVE TRIP TIME AT 15.0 × PU
176E
FLEXCURVE TRIP TIME AT 15.5 × PU
176F
FLEXCURVE TRIP TIME AT 16.0 × PU
1770
FLEXCURVE TRIP TIME AT 16.5 × PU
1771
FLEXCURVE TRIP TIME AT 17.0 × PU
1772
FLEXCURVE TRIP TIME AT 17.5 × PU
1773
FLEXCURVE TRIP TIME AT 18.0 × PU
1774
FLEXCURVE TRIP TIME AT 18.5 × PU
1775
FLEXCURVE TRIP TIME AT 19.0 × PU
1776
FLEXCURVE TRIP TIME AT 19.5 × PU
1777
FLEXCURVE TRIP TIME AT 20.0 × PU
1778
1779
OVERCURRENT CURVE MULTIPLIER
177B
OVERCURRENT CURVE RESET
CURRENT ELEMENTS / PHASE DIFFERENTIAL
17E0
PHASE DIFFERENTIAL TRIP
17E1
ASSIGN TRIP RELAYS (1-4)
17E2
DIFFERENTIAL TRIP MIN. PICKUP
17E3
DIFFERENTIAL TRIP SLOPE 1
17E4
DIFFERENTIAL TRIP SLOPE 2
17E5
DIFFERENTIAL TRIP DELAY
CURRENT ELEMENTS / GROUND DIRECTIONAL
1800
SUPERVISE WITH DIGITAL INPUT
6
1801
GROUND DIRECTIONAL MTA
1802
GROUND DIRECTIONAL ALARM
1803
ASSIGN ALARM RELAYS (2-5)
1804
GROUND DIR. ALARM PICKUP
1805
GROUND DIR. ALARM DELAY
1806
GROUND DIR. ALARM EVENTS
1807
GROUND DIRECTIONAL TRIP
1808
ASSIGN TRIP RELAYS (1-4)
1809
GROUND DIR. TRIP PICKUP
180A
GROUND DIR. TRIP DELAY
CURRENT ELEMENTS / HIGH-SET PHASE O/C
1830
HIGH-SET PHASE O/C TRIP
1831
ASSIGN TRIP RELAYS (1-4)
1832
HIGH-SET PHASE O/C PICKUP
1833
HIGH-SET PHASE O/C DELAY
VOLTAGE ELEMENTS / UNDERVOLTAGE
2000
UNDERVOLTAGE ALARM
2001
ASSIGN ALARM RELAYS (2-5)
2002
UNDERVOLTAGE ALARM PICKUP
2003
UNDERVOLTAGE ALARM DELAY
2004
UNDERVOLTAGE ALARM EVENTS
2005
UNDERVOLTAGE TRIP
2006
ASSIGN TRIP RELAYS (1-4)
2007
UNDERVOLTAGE TRIP PICKUP
2008
UNDERVOLTAGE TRIP DELAY
1, 2, 3
See Table footnotes on page 6–39
6-26
RANGE
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 100000
0 to 1
0 to 2
0 to 3
5 to 100
1 to 100
1 to 100
0 to 100
0 to 1
0 to 3
0 to 2
1 to 4
5 to 2000
1 to 1200
0 to 1
0 to 2
0 to 3
5 to 2000
1 to 1200
0 to 2
0 to 3
15 to 2000
0 to 10000
0 to 2
1 to 4
50 to 99
2 to 1200
0 to 1
0 to 2
0 to 3
50 to 99
2 to 100
489 Generator Management Relay
6 COMMUNICATIONS
STEP
UNITS
FORMAT
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
F14
1
F201
1
F115
1
F50
× CT
1
F3
1
%
F1
1
%
F1
1
cycles
F1
1
F103
1
F217
1
F115
1
F50
× CT
1
F3
1
s
F2
1
F105
1
F115
1
F50
× CT
1
F3
1
s
F2
1
F115
1
F50
× CT
1
F3
1
s
F3
1
F115
1
F50
× Rated
1
F3
1
s
F2
1
F105
1
F115
1
F50
× Rated
1
F3
1
s
F2
GE Power Management
DEFAULT
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
100
0
0
1
10
10
20
0
1
0
0
16
5
30
0
0
1
5
30
0
1
500
100
0
16
85
30
0
0
1
80
10

Advertisement

Table of Contents
loading

Table of Contents