4.9 S8 RTD TEMPERATURE
T
RTD #1
T
[ENTER] for more
4
RTDs 1 through 6 default to Stator RTD type. There are individual alarm and trip configurations for each RTD. This allows
one of the RTDs to be turned off if it malfunctions. The alarm level is normally set slightly above the normal running temper-
ature. The trip level is normally set at the insulation rating. Trip voting has been added for extra reliability in the event of
RTD malfunction. If enabled, a second RTD must also exceed the trip temperature of the RTD being checked before a trip
will be issued. If the RTD is chosen to vote with itself, the voting feature is disabled. Each RTD name may be changed if
desired.
4-46
ð
RTD #1 APPLICATION:
ENTER
Stator
ESCAPE
RTD #1 NAME:
ESCAPE
MESSAGE
RTD #1 ALARM:
ESCAPE
Off
MESSAGE
ASSIGN ALARM
ESCAPE
RELAYS (2-5): ---5
MESSAGE
RTD #1 ALARM
ESCAPE
TEMPERATURE: 130°C
MESSAGE
RTD #1 ALARM
ESCAPE
EVENTS: Off
MESSAGE
RTD #1 TRIP:
ESCAPE
Off
MESSAGE
RTD #1 TRIP VOTING:
ESCAPE
RTD #1
MESSAGE
ASSIGN TRIP
ESCAPE
RELAYS (1-4): 1---
MESSAGE
RTD #1 TRIP
ESCAPE
TEMPERATURE: 155°C
MESSAGE
489 Generator Management Relay
4 SETPOINT PROGRAMMING
Range: Stator, Bearing, Ambient, Other, None
Range: 8 alphanumeric characters
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to 5.
Range: 1 to 250°C in steps of 1
Range: On, Off
Range: Off, Latched, Unlatched
Range: RTD #1 to RTD #12
Range: Any combination of Relays 1 to 4
Range: 1 to 250°C in steps of 1
GE Power Management

4.9.2 RTDS 1 TO 6