6.3 MEMORY MAP
Table 6–2: DATA FORMATS (Sheet 3 of 5)
FORMAT
TYPE
CODE
F129
Unsigned
16 bit integer
F130
Unsigned
16 bit integer
F131
Unsigned
16 bit integer
F132
Unsigned
16 bit integer
F133
Unsigned
16 bit integer
F134
Unsigned
16 bit integer
6
6-42
DEFINITION
Analog input selection
0 = Disabled, 1 = 4-20 mA, 2 = 0-20 mA, 3 = 0-1 mA
Pickup type
0 = Over, 1 = Under
Input switch status
0 = Closed, 1 = Open
Trip coil supervision status
0 = No Coil, 1 = Coil
Generator status
0 = Offline, 1 = Offline, 2 = Online, 3 = Overload, 4 = Tripped
Cause of event / Cause of trip
VALUE PARAMETER
0
No Event
1
General Sw. A Trip
2
General Sw. B Trip
3
General Sw. C Trip
4
General Sw. D Trip
5
General Sw. E Trip
6
General Sw. F Trip
7
General Sw. G Trip
8
Sequential Trip
9
Tachometer Trip
10
UNKNOWN TRIP
11
UNKNOWN TRIP
12
Overload Trip
13
UNKNOWN TRIP
14
Neutral O/V Trip
15
Neut. U/V (3rd) Trip
16
17
18
19
20
Differential Trip
21
Acceleration Trip
22
RTD 1 Trip
23
RTD 2 Trip
24
RTD 3 Trip
25
RTD 4 Trip
26
RTD 5 Trip
27
RTD 6 Trip
28
RTD 7 Trip
29
RTD 8 Trip
30
RTD 9 Trip
31
RTD 10 Trip
32
RTD 11 Trip
33
RTD 12 Trip
34
Undervoltage Trip
35
Overvoltage Trip
36
Phase Reversal Trip
37
Overfrequency Trip
38
Power Factor Trip
39
Reactive Power Trip
40
Underfrequency Trip
41
Analog I/P 1 Trip
42
Analog I/P 2 Trip
43
Analog I/P 3 Trip
44
Analog I/P 4 Trip
45
Single Phasing Trip
46
Reverse Power Trip
489 Generator Management Relay
VALUE PARAMETER
47
Field-Bkr Discrep.
48
Offline O/C Trip
49
Phase O/C Trip
50
Neg. Seq. O/C Trip
51
General Sw. A Alarm
52
General Sw. B Alarm
53
General Sw. C Alarm
54
General Sw. D Alarm
55
General Sw. E Alarm
56
General Sw. F Alarm
57
General Sw. G Alarm
58
59
Tachometer Alarm
60
Thermal Model Alarm
61
Overload Alarm
62
Underfrequency Alarm
63
64
Ground Fault Alarm
65
RTD 1 Alarm
66
RTD 2 Alarm
67
RTD 3 Alarm
68
RTD 4 Alarm
69
RTD 5 Alarm
70
RTD 6 Alarm
71
RTD 7 Alarm
72
RTD 8 Alarm
73
RTD 9 Alarm
74
RTD 10 Alarm
75
RTD 11 Alarm
76
RTD 12 Alarm
77
Open RTD Alarm
78
Short/Low RTD Alarm
79
Undervoltage Alarm
80
Overvoltage Alarm
81
Overfrequency Alarm
82
Power Factor Alarm
83
Reactive Power Alarm
84
Low Fwd Power Alarm
85
Trip Counter Alarm
86
Breaker Fail Alarm
87
Current Demand Alarm
88
kW Demand Alarm
89
kvar Demand Alarm
90
kVA Demand Alarm
91
Broken Rotor Bar
92
Analog I/P 1 Alarm
93
Analog I/P 2 Alarm
6 COMMUNICATIONS
VALUE PARAMETER
94
Analog I/P 3 Alarm
95
Analog I/P 4 Alarm
96
Reverse Power Alarm
97
Incomplete Seq.Alarm
98
Negative Seq. Alarm
99
Ground O/C Alarm
100
101
Service Alarm
102
Control Power Lost
103
Cont. Power Applied
104
Thermal Reset Close
105
Emergency Rst. Open
106
Start While Blocked
107
Relay Not Inserted
108
Trip Coil Super.
109
Breaker Failure
110
VT Fuse Failure
111
Simulation Started
112
Simulation Stopped
113
Ground O/C Trip
114
Volts/Hertz Trip
115
Volts/Hertz Alarm
116
Low Fwd Power Trip
117
Inadvertent Energ.
118
Serial Start Command
119
Serial Stop Command
120
Input A Control
121
Input B Control
122
Input C Control
123
Input D Control
124
Input E Control
125
Input F Control
126
Input G Control
127
Neutral O/V Alarm
128
Neut. U/V 3rd Alarm
129
Setpoint 1 Active
130
Setpoint 2 Active
131
Loss of Excitation 1
132
Loss of Excitation 2
133
Gnd. Directional Trip
134
Gnd. Directional Alarm
135
HiSet Phase O/C Trip
136
Distance Zone 1 Trip
137
Distance Zone 2 Trip
138
Dig I/P Wavefrm Trig
139
Serial Waveform Trig
GE Power Management