1.2 SPECIFICATIONS
CASE
Drawout:
1
Seal:
Door:
Mounting:
IP Class:
PRODUCTION TESTS
Thermal Cycling:
Dielectric Strength:
DO
NOT
SAFETY GROUND DURING TEST!
WARNING
FUSE
Current Rating:
Type:
Model#:
An external fuse must be used if supply voltage
exceeds 250V
WARNING
1-8
Fully drawout (Automatic CT shorts)
Seal provision
Dust tight door
Panel or 19" rack mount
IP20-X
Operational test at ambient, reducing to
–40°C and then increasing to 60°C
2.0 kV for 1 minute from relays, CTs,
VTs, power supply to Safety Ground
CONNECT
FILTER
GROUND
3.15 A
5 × 20 mm Slo-Blo Littelfuse, High
Breaking Capacity
215.315
489 Generator Management Relay
TYPE TESTS
Dielectric Strength:
DO NOT CONNECT FILTER GROUND TO SAFETY
GROUND DURING TEST
WARNING
Insulation Resistance:
DO
NOT
SAFETY GROUND DURING TEST
WARNING
TO
Transients:
Impulse Test:
RFI:
EMI:
Static:
Humidity:
Temperature:
Environment:
Vibration:
PACKAGING
Shipping Box:
Shipping Weight:
CERTIFICATION
ISO:
UL:
CSA:
CE:
1 INTRODUCTION
Per IEC 255-5 and ANSI/IEEE C37.90.
2.0 kV for 1 minute from relays, CTs,
VTs, power supply to Safety Ground
IEC255-5 500 V DC, from relays, CTs,
VTs, power supply to Safety Ground
CONNECT
FILTER
GROUND
ANSI C37.90.1 oscillatory (2.5 kV/
1 MHz); ANSI C37.90.1 Fast Rise (5 kV/
10 ns); Ontario Hydro A-28M-82;
IEC255-4 Impulse/High Frequency Dis-
turbance Class III Level
IEC 255-5 0.5 Joule 5 kV
50 MHz / 15 W Transmitter
C37.90.2 Electromagnetic Interference
at 150 MHz and 450 MHz, 10V/m
IEC 801-2 Static Discharge
90% non-condensing
–40°C to +60°C ambient
IEC 68-2-38 Temperature/Humidity cycle
Sinusoidal Vibration 8.0 g for 72 hrs.
12" × 11" × 10" (W × H × D)
30.5cm × 27.9cm × 25.4cm
17 lbs Max / 7.7 kg
Manufactured under an ISO9001 regis-
tered system.
UL
CSA
Conforms to IEC 947-1, IEC 1010-1