Install the Telescopic Rail Runners on the Rack
Rack Rail Runners require a minimum of 48 cm and a maximum of 80cm within the rack for installation.
Procedure
To install the Telescopic rail runners on the rack:
1. Determine the location of the Collaboration Server on the rack:
•
Allow for a 1U gap above and below the system for ventilation.
•
Use the Rack Spacer (item no. 3) to predetermine its position on the rack post, making sure
that square studs of the spacer fit into the rack post's square/rounded mounting holes. Mark
the spacer's location on the rack post. Repeat this process for the 3 remaining vertical posts
ensuring that the system can be horizontally seated.
Front view of RealPresence Collaboration Server (RMX) 2000/4000 rail runner assembly
2. Position the Rack Spacer (3) onto the marked rack post together with left rack rail runner
(item no. 1 which is labeled LEFT) and fasten the flat head screws 3*10 mm (4) as shown in the
following figure.
Polycom, Inc.
Item
no.
Item Sample
8
9
Installation Preparations
Item
Quantity
2
2
19