Connect The Rmx 4000 To Power Sources; Connect The Rmx 4000 To Ac Power - Polycom RealPresence RMX 4000 Hardware Manual

Collaboration server
Hide thumbs Also See for RealPresence RMX 4000:
Table of Contents

Advertisement

Installing the handles and brackets & detailed rear view of 23" bracket attachment
3. Mount the RealPresence Collaboration Server (RMX) 4000 on top of the rack brackets using the
blades or place it on a rack mount shelf with chassis runners.
4. Fasten the RealPresence Collaboration Server (RMX) 4000 to the rack with eight screws into the
holes provided on the RealPresence Collaboration Server (RMX) 4000 front as shown in figure
above.
Rack mounting screws must be supplied by the rack manufacturer.
Warning:
The procedures of reverse mounting RealPresence Collaboration Server (RMX) 4000 from 23"
brackets to 19" brackets are the same with the procedures described above.

Connect the RMX 4000 to Power Sources

You can connect either an AC or a DC powers according to the power system required at your site.
The following restrictions apply to the conductors and connectors that may be used to ground the unit
when rack mounted:
When using bare conductors, they must be coated with an appropriate antioxidant compound
before crimp connections are made. Tinned, solder-plated or silver-plated connectors do not have
to be prepared in this manner.
The same bolt assemblies should not secure multiple connectors.
Listed fastening hardware must be compatible with the materials being joined and must be preclude
loosening, deterioration and electrochemical corrosion of the hardware and joint materials.

Connect the RMX 4000 to AC power

For systems with AC Power, up to three power supplies can be installed with one being redundant.
To connect the Collaboration Server 4000 to AC power:
Procedure
1. Make sure that the power button is switched OFF on the RealPresence Collaboration Server
(RMX) 4000.
Polycom, Inc.
Ground connection
When the unit is installed on a rack, the rack must be properly grounded to
the central office ground. The rack must be grounded with two-hole
compression-type connectors using copper conductors (tinned or untinned).
Wire, bus bar or braided strap connectors are acceptable.
RMX 4000 Installation
26

Advertisement

Table of Contents
loading

Table of Contents