Siemens SIMOTION C230-2 Equipment Manual page 98

Hide thumbs Also See for SIMOTION C230-2:
Table of Contents

Advertisement

Wiring
Shield connecting element
This element can be inserted in the mounting rail to provide screening for shielded
cables. It can accommodate up to eight shielding terminals.
See Section 6.3
Connection of measuring inputs or proximity encoders (BEROs)
Proceed as follows:
1. Wire the power supply for the encoders. These must meet the same criteria as
the load power supply for the C230-2.
2. Connect the shielded signal line to the encoders.
3. Remove a sufficient length of the cable sheath at the control end so that you
can connect the shield to the shield connecting element and the free cable ends
to the front connector.
4. Wire the signal line to the front connector.
C230-2
Fig. 6-11
Note
For the assignment of the front connector and the description of the I/O interface,
refer to Subsection 3.1.8.
6-98
X1
22
23
24
25
26
27
Shield routed to shield
connecting element
40
Overview of connections for measuring inputs or proximity switches
L+
M
external
E Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
+
+
+
+
+
+