Wiring
Fitting the shield connecting element
Fit the shield connecting element as follows:
1. Push the two threaded studs for the retaining bracket into the guide on the un-
derside of the rail. Position the retaining bracket under the modules to be wired.
2. Screw the retaining bracket tight on the mounting rail.
3. A slotted web is fitted on the underside of the shielding terminal. Fit the shield-
ing terminal on edge a of the retaining bracket in this position (see Fig. 6-12).
Press the shielding terminals down and pivot them into the required position.
You can fit a maximum of four shielding terminals on each of the two rows.
Fig. 6-12
Laying the cables
Only one or two shielded wires per shielding terminal may be attached (see
Table 6-3). Connect the cable to the stripped cable shield. The stripped section of
cable shield must have a minimum length of 20 mm. If you require more than four
shielding terminals, start the wiring on the back row of the shield connecting ele-
ment.
Tip: Make sure you allow a sufficient length of cable between the shielding termi-
nal and the front connector. This will, for example, ensure that if a repair is re-
quired, you can unplug the front connector without also having to remove the
shielding terminal.
6-100
Shielding terminal
Fitting the shield connecting element
Retaining bracket
Edge a