Overall reset using the mode selector
Proceed as follows (see Fig. 8-2):
1. Turn the key on the mode selector to the STOP position.
2. Turn the key to the MRES position. Hold the key in this position until the STOP
LED changes from flashing to permanently illuminated.
3. Within 3 seconds, you must release the switch and return it to the MRES posi-
tion. The overall reset procedure is executed. All LEDs illuminate during this
time. The C230-2 has completed the overall reset procedure when the STOP
LED illuminates.
The C230-2 has completed the overall reset procedure.
STOP LED
On
Off

Fig. 8-2
Sequence in which the mode selector is operated to perform an overall reset
E Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
3 s
Max. 3 s

All LEDs on

Commissioning
t
8-119