Wiring
Wiring with the power connector
Proceed as follows to wire the PS 307 power supply module and the C230-2:
Warning
!
You could come into contact with live wires if the power supply module and any
additional load power supplies are switched on.
Ensure that the system is de-energized when you wire the system!
1. Open the front covers of the PS 307 and the C230-2.
2. Release the clip for the cable strain relief on the PS 307.
3. Strip the mains cable (230 V/120 V) (strip off 12 mm) and connect it to the
PS 307.
4. Tighten the clip for the cable strain relief.
5. Insert the power connector and screw it tight.
6. Close the front doors.
Cable strain relief
Power connector
Fig. 6-5
6-88
PS 307 C230-2
230 V/120 V
Connecting power supply module and C230-2 with power connector
4
0.5 to 0.8 Nm
E Siemens AG, 2003 All rights reserved