Device Data
Digital outputs (according to IEC 1131-2/DIN EN 61131-2)
Number of outputs
Supply voltage
Output voltage
Max. output current
Aggregate current of outputs
Extinguishing energy per output
Lamp load
Switching frequency
Short-circuit protection
Max. leakage current
Output delay (Q0...Q7)
Electrical isolation between out-
puts
Electrical isolation between out-
puts and logic
Isolation
1) V
– Supply voltage of outputs
L
Note
The connection cable between the voltage source and the load current supply con-
nector L+ and the associated reference potential M should not exceed a maximum
length of 10 m.
READY output (RDY)
Table 3-15 Electrical parameters of RDY contact assembly
Contact assembly RDY
Switching voltage DC
Switching current
Switching capacity
Mechanical service life
Electrical service life
3-54
8
24 VDC (permissible range: V
1)
1-signal: From V
– 0.8 V to V
L
1-signal: 5 mA...0.6 A (via supply voltage)
S
Max. 4 A (at 0... 40°C )
S
Max. 2 A (at 40...55°C)
400 mJ (not simultaneous)
5 W
S
100 Hz (with resistive load)
S
2 Hz (with inductive load)
Yes
0-signal: 2 mA
S
0 → 1-signal: 500 µs (type 150 µs) at RL = 60 Ohm
S
1 → 0-signal: 500 µs (type 150 µs) at RL = 60 Ohm
No
Yes
500 V
Max. 50 V
Max. 1 A
Max. 30 VA
Usually 10
9
Usually 3*10
E Siemens AG, 2003 All rights reserved
= 20.4...28.8 V)
L
1)
V
L
switching cycles
6
switching cycles at 24 V/1 A
SIMOTION C230-2, 04.2003 Edition